Short-circuit Icc

Three-phase fault current per IEC 60909

Panduan Teknis & Teori
Icc determines required breaker breaking capacity Icu. Impedance chain: utility → transformer → cable.
UPSTREAM SOURCE
Short-circuit MVA at HV side. Urban: 250–500. Rural: 50–150.
TRANSFORMER
Typical: 4 % (≤250 kVA), 5 % (≤630), 6 % (≤1250), 7 % (≥1600)
CABLE TO FAULT (OPTIONAL)
Leave blank for fault at transformer terminals